The Bio- gas flare
Sharing
                                        
                                    Product Description
                                
Technical Feature
- Double probe type high-voltage ignition,high reliability
 - Ultraviolet flame detector and temperature detection double monitoring
 - Flame arrester
 - High temperature ceramic fiber insulation layer
 - The combustion efficiency:99.0%
 - The natural wind and the forced purge air combination
 - Stainless steel flare disc and burner
 - Purge air staging combustion
 
Specifications
- Methane concentration: 30%-60%
 - Combustion temperature:500-1200℃
 - Residence time:> 0.3S
 - Turn down range:20%-100%
 - Inlet gas pressure:> 2Kpa
 - Sound pressure at full load: less than 85dB
 - No open flame combustion, low heat radiation.
 
Standard Specifications
| Model | 
					Max.Capacity (Nm3/h)  | 
				Flange Connection | Pressure | Size(D*H) | Mounting Dimensions | Mounting holes | Ignition electrodenumber | Weight(kg) | 
|---|---|---|---|---|---|---|---|---|
| INTERNAL-300E | 300 | DN80/PN10 | >2KPa | ?1000*7000 | ?850 | 8-M30 | 1 | 2500 | 
| INTERNAL-600E | 600 | DN125/PN10 | >2KPa | ?1200*7000 | ?1050 | 8-M30 | 1 | 2800 | 
| INTERNAL-1000E | 1000 | DN150/PN10 | >2KPa | ?1400*8000 | ?1200 | 8-M30 | 1 | 3500 | 
| INTERNAL-1500E | 1500 | DN200/PN10 | >2KPa | ?1600*8000 | ?1400 | 8-M30 | 1 | 4800 | 
| Note: Consult factory for different media can be specific selection | ||||||||
	
	
 
	